I have a Class T at the battery. Does the inverter feed off the busbar need its own fuse?
The two fuses are doing different jobs, which is why you need both.
What each one protects
A fuse protects the cable it is fitted to. That is its entire purpose.
The fuse at the battery protects the big cable between the battery and the distribution point, and on a lithium bank it is also the fuse carrying the interrupt rating. Victron's requirement is unambiguous: in every lithium installation at least one fuse in the DC line must have an interrupt rating equal to or greater than the maximum prospective short-circuit current of the bank, and they describe that as mandatory. Class T is the usual answer because its interrupt rating is far above the alternatives.
The fuse on the inverter branch protects the inverter's own cable. That cable is smaller than the main battery cable, so the battery fuse is too large to protect it. A short in the inverter feed would run at a current the main fuse happily passes while the branch cable cooks.
Victron's selection rule covers this directly: with a single consumer on a circuit the fuse matches the consumer's rating or the cable's rating, whichever is lower. With multiple consumers, it matches the cable.
The multi-inverter rule, which is the same rule
Victron is specific about systems with more than one inverter or inverter/charger:
- Fuse each unit individually, using the same fuse type for each so every DC path has the same resistance.
- Do not use one large fuse for the whole system. A fault inside a single inverter rarely draws enough current to trip an oversized fuse, so the current keeps flowing at a dangerous level and damages wiring instead of blowing the fuse.
That second point is the honest reason the branch fuse exists. It is not redundancy.
Does the branch fuse also have to be Class T?
Not necessarily. The interrupt-rating requirement is satisfied by at least one fuse in the DC line, and that is the job of the one at the battery. The branch fuse is chosen for current rating, DC voltage rating and speed.
For an inverter feed you want a slow fuse, because inverters have large input capacitors and a high inrush. MEGA fuses are slow; ANL fuses are fast. Read the DC voltage rating rather than the AC one, and note that many DC fuses suit 12 V and 24 V but are not rated for 48 V and above.
Getting the distribution right
Run everything to a distribution point rather than stacking ring terminals on a battery post. The cross-section of the cable feeding the busbar must equal the sum of the cross-sections required by everything fed from it, or the busbar is a hidden bottleneck.
A plain busbar works for straightforward distribution. Where each branch needs its own protection, the six-way MEGA fuse holder with an integrated busbar does both jobs in one part, and the Lynx Distributor does it modularly. The Lynx Class-T Power In is the Victron module built to put the Class T at the head of that chain.
One last thing: busbars are not insulated. Shield them. A dropped spanner across an unshielded pair of busbars on a lithium bank is a very serious event.
Send us your bank size, your inverter and your cable lengths and we will check the fusing with you. Everything ships from Upland, California.
Related guides
What you need
-
Victron Busbar | DC Distribution
$24.00
-
Victron Six-Way MEGA-fuse Holder with Busbar | 250A | CIP050060000
$47.00
-
Victron MEGA-fuse
$65.00
-
Victron Fuse Holder for MEGA-fuse | CIP000100001
$18.00
-
Victron Lynx Distributor | DC Busbar & Fuse Holder | LYN060102010
$284.00
-
Victron Lynx Power In & Lynx Class-T Power In | DC Busbar
$190.00
Want the full walkthrough? Read the complete guide.