Which Black Series circuit breaker do I need: 50A inline, 10/15A or 20A?
Short answer: Match the one you are replacing. The 20A (RVP-00200) is a 120V AC plug-in breaker for the AC panel. The 50A inline (RVP-00162) is a manual-reset breaker on heavy 12V DC cable. The stud-type 10A or 15A (RVP-00191) is a 12V auto-reset breaker. Read the rating printed on your old one and never go higher.
Black Series RVs use three different breakers, on two different electrical systems. They are not interchangeable, so start by working out which system the tripped one sits on.
Tell them apart
| 20A breaker | 50A inline breaker | 10A/15A auto-reset | |
|---|---|---|---|
| Part | RVP-00200 | RVP-00162 | RVP-00191 |
| System | 120V AC | 12V DC | 12V DC |
| Where you find it | plugged into the AC breaker panel | inline on a heavy 12V cable | surface-mounted, wired to two studs |
| Looks like | 1 in wide Type QP plug-in | black body, red trip lever, red reset button, covered terminals | grey body, two threaded studs (one copper, one zinc), two mounting holes |
| After it trips | flip it back | press the reset button | resets itself once the overload clears |
| Listed for | kitchen, A/C, microwave, bathroom and slide-out circuits | heavy 12V DC cables | 12V branch circuits |
The rating rule
A breaker protects the wire behind it, not the appliance. The 20A listing puts it plainly: match breaker amperage to wire size. So:
- Read the rating printed on the old breaker. The auto-reset one in our photo is marked T1/10A/12V; yours may say 15A. Put the rating you need in the order notes for RVP-00191.
- Never fit a higher rating because the old one kept tripping. The 20A takes 14 to 10 AWG wire; a larger breaker on the same wire lets it overheat before anything trips.
Repeated tripping is a symptom
- Auto-reset 10A/15A cycling on and off: something on that 12V circuit is drawing too much or shorting. The breaker will keep resetting into the fault, so find it rather than replacing the breaker first.
- 50A inline won't stay reset: check the heavy cable run and whatever it feeds before resetting again. That is what the manual reset is for: power stays off until you have looked.
- 20A AC tripping: look at what was running on that circuit when it went; its listing covers kitchen, A/C, microwave, bathroom and slide-out circuits.
If the old breaker is cracked, scorched or the reset no longer latches, replace it like for like. Email support@rvpartsgiant.com a photo of the old part and your model if the markings are worn off.
What you need
Want the full walkthrough? Read the complete guide.