Shop this guide
→ RecPro 50 amp male replacement plug end
→ RecPro 50 amp locking female replacement plug
A 50 amp RV cord carries a lot of power. If the plug is melted, discolored, cracked or loose on its pins, stop using it. A damaged plug end can overheat and start a fire. Replacing the plug end is a common repair, but it's high-voltage work. If you're not comfortable wiring a 240-volt plug, have an electrician or RV technician do it.
Male or female end?
- Male end: the four-prong plug that goes into the campground pedestal. Replace it with the RecPro 50 amp male plug end.
- Female end: on a detachable cord, the locking connector that plugs into the RV's inlet. Replace it with the RecPro 50 amp locking female plug.
The four wires
A 50 amp RV cord follows the NEMA 14-50 layout: two 120 V hot legs, a neutral and a ground, giving 120/240 V service. Most RV cords use these colors and terminal markings, but always check the markings on your plug:
| Wire | Usual color | Terminal |
|---|---|---|
| Hot leg 1 | Black | X (brass) |
| Hot leg 2 | Red | Y (brass) |
| Neutral | White | W (silver) |
| Ground | Green | G (green) |
Step by step
- Disconnect all power. Unplug the cord from the pedestal and the RV, and switch off the pedestal breaker. Never work on a cord that's connected at either end.
- Cut off the damaged plug behind any melted or discolored section. If the heat damage runs up the cord, cut back until the copper is bright and the insulation is undamaged.
- Open the new plug and slide its housing and strain-relief clamp onto the cord first.
- Strip the outer jacket to the length the plug's instructions give, then strip each conductor to the marked length. Don't nick the copper strands.
- Connect each wire to its terminal (X, Y, W, G) and tighten the screws firmly. A loose terminal is what overheats and melts plugs. Make sure no stray strands touch a neighboring terminal.
- Close the housing and tighten the strain relief onto the outer jacket, not the individual wires, so pulling on the cord can't stress the terminals.
Test before you plug in
With the cord disconnected at both ends, use a multimeter on continuity. Each pin should connect to the matching pin at the other end of the cord. Check that no two conductors connect to each other. When you first connect to a pedestal, plug a surge protector or EMS with a wiring indicator in first. It will flag a crossed or open wire before power reaches your RV. If anything doesn't check out, have the cord tested by an electrician before use.
Prevent the next failure
Plugs usually burn because of a loose or corroded connection. Push plugs in fully, keep them dry and off the ground, and replace a pedestal adapter or plug that feels hot. For 30 amp setups, see our 30 amp cord safety guide.
FAQ
Can I replace a 50 amp plug with a 30 amp plug? Not as a repair. They're different services with different wiring. Use a proper 50-to-30 adapter if a site only has 30 amp.
Why did my 50 amp plug melt? Usually a loose or corroded pin or terminal creating heat under load. It's the reason to tighten terminals firmly and replace worn pedestal outlets or adapters.