Which Victron Autotransformer do I need for a 50-amp RV: 32A, 50A or 100A?

Answered by RV Parts Giant · Upland, CA · October 27, 2026

Short answer: Choose by pass-through current. A 50-amp pedestal is 50A on each leg, so it needs the 100A model (or the 50A version we list); the 32A unit suits a 30-amp feed or a single inverter. What the rating does not change is the balancing: every model carries the same toroid, which can only move 28A continuously (32A for 30 minutes) from one leg to the other.

The number on a Victron Autotransformer is its pass-through rating: the current that goes straight through the two-pole input breaker without being transformed. Victron's manual is blunt that the transformer inside is identical in every model. That one fact settles most sizing questions.

What each model passes through

Model Breaker and feed-through Use it for
32A 32A, two pole A 30-amp shore cord, or a single 120V or 240V inverter up to about 3.8 kVA
50A (listed version) 50A pass-through per our listing A 50-amp pedestal with no headroom to spare
100A 100A, two pole A 50-amp pedestal, generator or stacked inverters with margin

A 50-amp RV service is 50A on each of two 120V legs. The 32A model's breaker would trip long before the pedestal's, so for a 50-amp coach the choice is the 50A or 100A unit.

What no model changes: 28A of balancing

The windings can carry 32A for 30 minutes (3,800 VA) and 28A continuously at 40°C. That is the most current the autotransformer can shift from a lightly loaded leg to a heavy one, or convert between 120V and 240V. Victron's worked example: a 240V 5 kVA inverter feeding a 32A autotransformer gives 21A of balanced load on each 120V leg, and one leg can run up to 38.5A only while the other stays at 3.5A or less. Buying the 100A model buys breaker capacity, not more balancing.

So if your plan is "run the roof air on one leg and nothing on the other", check that the difference between the legs stays under 28A. If it will not, the fix is two inverters stacked for split phase, not a bigger autotransformer.

The ground relay

In inverter mode the inverter's neutral must be bonded to ground for the GFCI to work. The autotransformer has a grounding relay built in for this, driven by the 230/240V MultiPlus or Quattro, and the inverter's own internal ground relay has to be disabled when you use it. If you are balancing a generator instead, the generator's neutral should be grounded and the relay stays unused.

Practical limits

  • Indoor or compartment mounting only: it is IP21 and needs 4 in of clear space for ventilation. Any orientation works; vertical sheds heat best.
  • Screw terminals take up to 35 mm² (AWG 2). Size the wire to the breaker, not the load.
  • Over-temperature shutdown disconnects it from the supply and the reset is manual.
  • It does not provide isolation. If you need an isolated shore connection, that is a different product.
  • 12.5 kg for the 32A, 13.5 kg for the 100A, both 425 x 214 x 110 mm, with a 5-year warranty.

One data note: our listing shows a shorter case for the 32A and 50A units than Victron's current manual, which gives the same enclosure for both models. Plan the space around the manual's dimensions until we confirm.

Autotransformers, MultiPlus-II and Quattro units ship from our Upland, California warehouse.